Skip to main content

Open items

Resolve before final sign-off. Keep this list in sync with the BOM/SLD open-item register.

Safety & scope

  • Man-rated or payload-only? — determines Option C, cockpit E-stop, brake redundancy and formal ISO 13849-2 validation. Resolve first.
  • AX5801 compatibility with delivered drive HW revision
  • -K2 / -K3 230 V AC coil supply, protection and E-stop/PLC interlock (WD-001 coordination)

Main incomer & distribution

  • Prospective short-circuit current at incomer busbar vs. Q1 / RCCB breaking capacities
  • Site neutral (TN-S) confirmation; W101 25 mm² vs. GV3P73 terminal capacity
  • SPD Type 1+2 vs. Type 2 — customer site-condition sign-off
  • GV3P73 ↔ LC1D80P7 link kit part number
  • Q1 ↔ -K2 coordination/discrimination study — redo for Schneider pairing
  • -F7 iC60N exact catalog suffix
  • -F6 Easy9 EZ9R34240 swap decision (Type AC vs Type A for SMPS loads)
  • Q1 lockable door-coupling rotary operator (LOTO) part number
  • Total leakage current, 2× AX5118 + 1× AX5125 @ 3 m cable (AX5000 manual §8.9) vs. 300 mA
  • AX2090-NF50 sub-variant and per-drive vs. shared configuration

Mechanical / layout

  • Enclosure footprint re-verification with Schneider frame dimensions (800 → 1000 mm?)
  • Terminal marking convention change (CT-001)
  • Stage enclosure mass vs. gimbal balance budget

Slip rings & wiring

  • Data capsule rings: ≥ 8–10 channels, Ethernet-rated
  • PSU2/PSU3 3×380 V input capability
  • 36 A vs 35 A/ch: RMS analysis or TwinCAT ≤ 17 A limit — document choice
  • Slip ring derating at in-gimbal ambient; ≥ 380 V L-L between channels
  • Terminal designations vs. manuals for delivered hardware revisions
  • Conductor sizes vs. national code, measured run lengths, actual ambient